1. Introduction

Air Humidity measurement is a critical parameter across various industries, including HVAC, meteorology, agriculture, and manufacturing. Accurate determination of relative humidity (RH) is essential for optimizing environmental conditions, ensuring product quality, and enhancing operational efficiency. One widely adopted method for estimating RH involves measuring dry bulb temperature (DBT) and wet bulb temperature (WBT). This article explores the principles, techniques, and applications of humidity measurement using these temperatures, providing relevant calculations, and practical tools for implementation.

2. Fundamentals of Temperature and Humidity Measurement

2.1 Dry Bulb Temperature (DBT)

Dry bulb temperature (DBT) represents the ambient air temperature, independent of moisture content. Measured using a standard thermometer, DBT serves as a baseline for assessing air heat content. In psychrometric analysis, DBT is typically plotted on the x-axis, although different psychrometric charts may have slightly different orientations. Acceptable DBT ranges for office environments depend on clothing, activity level, and individual preferences. ASHRAE standards provide more specific guidance. Similarly, cool supply air temperature depends on the cooling load, system design, and desired room conditions.

2.2 Wet Bulb Temperature (WBT)

Wet bulb temperature (WBT) is measured using a thermometer with its bulb covered in a wet wick. As water evaporates from the wick, it cools the bulb, resulting in a lower temperature reading compared to DBT. WBT reflects the adiabatic saturation temperature and is influenced by air humidity and airflow. The difference between DBT and WBT indicates the air’s moisture content: a larger difference signifies drier air, while a smaller difference indicates nearly saturated air. Continuous airflow, typically achieved using a sling psychrometer, is essential for accurate WBT measurement.

2.2.1 Wet Bulb Wick Materials

High-quality wet bulb wicks are manufactured from cotton, ensuring optimal absorbency and hydrophilic properties. These wicks are designed to slide over thermometer bulbs or probes, facilitating accurate WBT measurements. Available in various thicknesses, they are widely used in HVAC, hatchery, and laboratory applications. While treated cotton wicks may offer better initial absorbency and resistance to mold growth, untreated cotton, if kept clean and properly wetted, can provide accurate results. The key is consistent evaporation. A typical range of wick thickness is 1/8 inch to 1/4 inch. The material and its ability to stay wet are more important than the thickness.

2.3 Dew Point Temperature (DPT)

Dew point temperature (DPT) is the temperature at which air becomes fully saturated, causing water vapor to condense. It is always lower than DBT and equals WBT at 100% RH. DPT is a key indicator of air moisture content and is plotted on the saturation line of psychrometric charts. In HVAC applications, understanding DPT is crucial for preventing condensation on surfaces such as windows, pipes, or chilled beams.

2.4 Humidity Concepts

Humidity refers to the concentration of water vapor in air, influenced by temperature and pressure. Key measurements include:

  • Absolute Humidity: Mass of water vapor per unit mass of dry air (e.g., lbm/lbm or kg/kg).
  • Relative Humidity (RH): Ratio of current water vapor pressure to saturation vapor pressure at a given temperature, expressed as a percentage.
  • Specific Humidity: Ratio of water vapor mass to the total mass of the air parcel (dimensionless or kg/kg dry air).

3. Advanced Humidity Measurement Techniques

3.1 Psychrometry

Psychrometry is the science of measuring humidity using thermodynamic principles. It relies on the relationship between temperature, moisture content, and air pressure. Psychrometric charts and calculations are essential tools for determining RH from DBT and WBT measurements.

3.2 Capacitive and Resistive Humidity Sensors

Modern humidity sensors, such as capacitive and resistive types, offer precise and reliable measurements. Capacitive sensors measure changes in dielectric constant due to moisture, while resistive sensors detect changes in electrical resistance of hygroscopic materials. These sensors are widely used in industrial and environmental applications. However, it's important to note that each type has its limitations. Capacitive sensors can be affected by contaminants, while resistive sensors may exhibit hysteresis. Accuracy and uncertainty should be considered when selecting a sensor.

3.3 Hygrometers

Specialized hygrometers, including chilled mirror dew point hygrometers and humidity generators, provide high-precision measurements. Chilled mirror hygrometers determine DPT by cooling a surface until condensation occurs, while humidity generators create controlled environments for calibration. Chilled mirror hygrometers are known for their high accuracy but can be expensive and require regular cleaning.

4. Estimating Relative Humidity from Dry and Wet Bulb Temperatures

4.1 Calculation Principles

Relative humidity is determined by the relationship between DBT, WBT, and atmospheric pressure, based on heat and mass transfer principles during evaporation. While the difference between DBT and WBT is an indicator, RH values are derived using psychrometric charts, equations, or software tools that account for these three parameters.

4.2 Psychrometric Chart: A Graphical Tool

A psychrometric chart is a graphical representation of the thermodynamic properties of moist air. It displays parameters such as DBT, WBT, RH, humidity ratio, enthalpy, specific volume, and DPT. This chart is essential for analyzing air properties and solving engineering problems related to HVAC, dehumidification, and ventilation.

4.2.1 Key Properties on the Psychrometric Chart

  • Enthalpy: The sum of sensible and latent heat in the air, represented by downward sloping green lines.
  • Specific Volume: The volume of moist air per unit mass, shown as downward sloping red lines.
  • Humidity Ratio: The ratio of water vapor mass to dry air mass, often expressed in grains of water vapor per pound of dry air.

4.2.2 Using the Psychrometric Chart

  1. Unit System Selection: Choose between SI (metric) or IP (imperial) units.
  2. Input Parameters: Enter DBT and a second parameter (WBT, RH, or DPT).
  3. Altitude Adjustment: Input altitude for accurate atmospheric pressure calculations.
  4. Results: Obtain values for atmospheric pressure, vapor pressure, humidity ratio, enthalpy, and specific volume.

4.3 Data Tables for RH Estimation

Due to the complex relationship between DBT, WBT, atmospheric pressure, and relative humidity, simplified data tables can be misleading. For accurate RH estimation, it is recommended to use a reliable online psychrometric calculators.

4.4 Example Calculation of Relative Humidity Using DBT and WBT

Problem Statement: Calculate the relative humidity (RH) given the following conditions:

Dry bulb temperature (DBT), \( T_{dbt} = 25^° ext{C} \)

Wet bulb temperature (WBT), \( T_{wbt} = 20^° ext{C} \)

Atmospheric pressure, \( p = 1013.25 \, ext{hPa} \) (standard atmospheric pressure at sea level)

Solution:

Step 1: Calculate the saturation vapor pressure at the dry bulb temperature (\( e_s(T_{dbt}) \)):

The Magnus formula is used to calculate the saturation vapor pressure at a given temperature:

\[ e_s(T) = 6.112 imes e^{\frac{17.67 imes T}{T + 243.5}} \

For \( T_{dbt} = 25^° ext{C} \):

\[ e_s(T_{dbt}) = 6.112 imes e^{\frac{17.67 imes 25}{25 + 243.5}} \
\[ e_s(T_{dbt}) = 6.112 imes e^{\frac{441.75}{268.5}} \
\[ e_s(T_{dbt}) = 6.112 imes e^{1.645} \
\[ e_s(T_{dbt}) pprox 6.112 imes 5.18 pprox 31.68 \, ext{hPa} \

Step 2: Calculate the saturation vapor pressure at the wet bulb temperature (\( e_s(T_{wbt}) \)):

For \( T_{wbt} = 20^° ext{C} \):

\[ e_s(T_{wbt}) = 6.112 imes e^{\frac{17.67 imes 20}{20 + 243.5}} \
\[ e_s(T_{wbt}) = 6.112 imes e^{\frac{353.4}{263.5}} \
\[ e_s(T_{wbt}) = 6.112 imes e^{1.341} \
\[ e_s(T_{wbt}) pprox 6.112 imes 3.82 pprox 23.34 \, ext{hPa} \

Step 3: Calculate the vapor pressure at the wet bulb temperature (\( e_w \)):

The formula for \( e_w \) is:

\[ e_w = e_s(T_{wbt}) - p imes (T_{dbt} - T_{wbt}) imes 0.00066 imes (1 + 0.00115 imes T_{wbt}) \

Substituting the values:

\[ e_w = 23.34 - 1013.25 imes (25 - 20) imes 0.00066 imes (1 + 0.00115 imes 20) \
\[ e_w = 23.34 - 1013.25 imes 5 imes 0.00066 imes 1.023 \
\[ e_w = 23.34 - 3.42 \
\[ e_w pprox 19.92 \, ext{hPa} \

Step 4: Calculate the relative humidity (RH):

The formula for RH is:

\[ RH = 100 imes rac{e_w}{e_s(T_{dbt})} \

Substituting the values:

\[ RH = 100 imes rac{19.92}{31.68} \
\[ RH pprox 62.9\% \

Conclusion: The relative humidity for the given dry bulb temperature of 25°C and wet bulb temperature of 20°C is approximately 62.9\%.

4.5 Software Tools for RH Estimation

Software tools like psychrometric chart calculators facilitate RH estimation by allowing users to input DBT and WBT values. These tools calculate RH and other psychrometric properties, supporting both SI and IP units.

5. Sling Psychrometer: A Practical Tool for RH Measurement

5.1 Design and Functionality

A sling psychrometer consists of two thermometers: one dry bulb and one wet bulb. The wet bulb is covered with a moistened wick to measure the cooling effect of evaporation. Mounted on a rotating handle, it is whirled in the air to facilitate evaporation and obtain accurate readings.

5.2 Usage Procedure

  1. Preparation: Moisten the wick with distilled water.
  2. Measurement: Whirl the psychrometer for 30–60 seconds.
  3. Reading: Record DBT and WBT after whirling.
  4. Calculation: Use psychrometric charts or software to determine RH.
  5. Repeat: Perform multiple readings for consistency.

5.3 Calibration and Maintenance

Regular calibration and maintenance are essential for accuracy. Calibration involves comparing the psychrometer readings to a traceable reference standard, such as a calibrated humidity sensor or a dew point hygrometer. Maintenance includes cleaning the wick with distilled water and replacing it if degraded.

6. Ensuring Measurement Accuracy

6.1 Calibration Techniques

Calibration ensures accuracy by comparing psychrometer readings to a traceable reference standard. This involves using a calibrated humidity sensor or a dew point hygrometer to verify the psychrometer's readings across its measurement range.

6.2 Environmental Considerations

Factors like temperature stability, air movement, and contaminants can affect measurements. Proper installation and protection of sensors are crucial.

6.3 Sensor Selection

Choosing the right sensor for the application, considering range, response time, and accuracy, is vital for reliable measurements.

6.4 Uncertainty Analysis and Error Sources

All measurements have inherent uncertainty. Potential error sources in DBT and WBT measurements include radiation effects on DBT, contamination of the wick, and insufficient airflow. Understanding and quantifying this uncertainty is crucial for reliable results.

7. Applications

7.1 HVAC and Energy Efficiency

DBT and WBT measurements optimize evaporative cooling, reducing energy consumption. Relevant standards include ASHRAE standards for HVAC applications.

7.2 Climate Monitoring

Provides critical data for weather forecasting and atmospheric studies.

7.3 Industrial Process Control

Ensures humidity control in industries like textiles, food processing, and pharmaceuticals.

7.4 Environmental Monitoring

Used in agriculture for crop management and in museums for artifact preservation.